Connecting the server to power

Before you begin

Ensure that proper power and grounding are available for all the power
outlets serving the CallPilot server and its associated peripherals. Power for
these devices must be wired and fused independently of all other
receptacles, and referenced to the same ground as the PBX system.
A qualified electrician must implement the single-point ground reference as
required between the power outlets of the CallPilot server and the power
outlets of the switch.
Provide a sufficient number of properly grounded power outlets or power
bars for all equipment. For more information, refer to grounding and power
requirements in this document and in the Planning and Engineering Guide
(555-7101-101).
The single-point ground (SPG) required by the system can be an isolated
ground (IG) bus or AC equipment ground (ACEG) bus in the service panel
or transformer. The system must be connected to safety ground/protective
earth in accordance with NEC requirements. For international use, the
system must be connected to safety ground/protective earth in accordance
with Paragraph 2.5 of EN60950/IEC950.
Note: Refer to Large System: Planning and Engineering (553-3021-120) for
a complete description of approved ground sources and methods. Insulated
ground wire must be used for system grounding.
1002rp Server Hardware Installation
Installing the server and connecting the peripheral devices
75