Electrical work

The electrical work should be performed by a specialist qualified for the work.
f Use the three phase power supply, and be sure to install the sub power distributing board for exclusive use with the unit
f
(separately purchased by the user).
❋ ❋ Avoid multiple connecting wiring as it can cause a drop in voltage, thus resulting in poor performance of the automatic
control circuit.
f Be sure to install circuit breaker (separately purchased by the user).
f
f Be sure to connect the grounding wire.
f
Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible
cord. (Code designation IEC:60245 IEC 66 / CENELEC:H07RN-F)
NOTE
1. Remove the screw on the electrical component box and remove the cover plate.
2. Route the connection cord through the side of the indoor unit and connect the cable to terminals.
3. Route the other end of the cable to the outdoor unit through the ceiling & the hole on the wall.
4. Reassemble the electrical component box cover, carefully tightening the screw.
Wiring standard
Model
Power
Circuit breaker
Below 20m
Electric wire
Below 50m
Allowable voltage
Min. size of electric wires from/to the
indoor/outdoor units
• You must compress the solderless ring to the cable and then connect it to the main power terminal.
• Solderless ring selection
CAUTION
Thickness of cable (mm
This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to
Ssc (*2) at the interface point between the user's supply and the public system. It is the responsibility of the installer
NOTE
or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the
equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to Ssc(*2).
[Ssc (*2)]
34
Mirage_AP50M0@_IBIM_EN_05323A-02.indd 34
Silver solder
)
2
2.5
Less than 9.5
4
Less than 9.5
MODEL
AP50M0AXXSG
AP50M1AXXSG
AP50M0✴ Series / AP50M1✴ Series
3N~, 380-415V, 50Hz
Earth leakage circuit breaker(ELCB) 30A
2.5mm
2
4mm
2
342~457V
Below 20m : 0.75mm
Over 20m : 1mm
2
B (mm)
d2 (mm)
More than 4.5
More than 4.5
Ssc[MVA]
0.528
0.528
2
2016-05-19 오후 1:27:21