Auxiliary Circuit Breaker
Distribution
Outdoor unit
Auxiliary
power
swich
❊ The designs and shape are subject to
change according to the model.

Electrical Work

14
E-
◆ Auxiliary circuit breaker should be installed near outdoor unit so that each
access is possible. Main/outdoor power supply cable are connected to
upper/lower terminal of auxiliary circuit breaker.
board
◆ It is necessary that the conduit kit for power supply to the outdoor
unit be installed between auxiliary power switch and the outdoor unit.
(the conduit kit is optional)
1
The supply voltage must be the same as the rated voltage of the
air conditioner.
2
Prepare the power souce for exclusive use with the air conditioner.
3
Use 15 amperes time delay fuse or circuit breaker.
MODEL
Power supply
Power cable
Assembly cable
Operating current(C)
Starting Current
Power consumption (C)
➢ When using the special NFB, use the NFB to bear the capacity of the air conditioner.
➢ Otherwise, the shot circuit in the NFB may occur.
➢ The power cable and the assembly cable are not supplied with the air conditioner.
AS07A5(6)MA
AS09A5(6)MAF
115V/60Hz
115V/60Hz
Single phase
Single phase
3G AWG 14
4G AWG 16
6.4
8.1
32A
43A
680W
950W
AS12AA(B)MCF
208-230V/60Hz
Single phase
5.4
31A
1230W