Electrical wiring work

Specification of the circuit breaker and power cable
Standard single (Heat Pump)
Model
AM080JXVAFH
AM100JXVAFH
AM120JXVAFH
AM140JXVAFH
AM160JXVAFH
AM180JXVAFH
AM200JXVAFH
AM220JXVAFH
AM240JXVAFH
AM260JXVAFH
❋ When installing outdoor units in module, select the power supply cable according to the sum of outdoor unit capacity.
(Refer to the table for each model.)
❋ Power Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible
cord. (Code designation IEC: 60245 IEC 66 / CENELEC: H07RN-F)
Standard single (Heat Pump)
Model
AM080JXVAJH/AZ
AM100JXVAJH/AZ
AM120JXVAJH/AZ
AM140JXVAJH/AZ
AM160JXVAJH/AZ
AM180JXVAJH/AZ
AM200JXVAJH/AZ
AM220JXAVJH/AZ
❋ When installing outdoor units in module, select the power supply cable according to the sum of outdoor unit capacity.
(Refer to the table for each model.)
❋ Power Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible
cord. (Code designation IEC: 60245 IEC 66 / CENELEC: H07RN-F)
56
MCA
28.0
34.0
36.0
50.0
56.1
66.5
73.0
70.0
70.0
73.0
MCA
17.4
18.9
20.6
25.0
28.1
33.8
41.8
46.0
MFA
40
50
50
63
63
75
80
80
80
80
MFA
25
25
32
32
40
50
63
63