Connection of refrigerant piping
Flare processing
1. Cut the pipe using the pipe cutter.
2. Remove burr on the edge of pipe.
- If burr is not removed after cutting the pipe, there is a risk of refrigerant gas leakage.
- If foreign substance such as burr goes into the pipe, there is a risk of product
breakdown. Face the pipe downward when doing the work.
3. Insert the flare nut into the pipe, and then perform the flare processing.
Correct
When installing, make sure there is no leakage. When recovering the refrigerant, ground the compressor first before
removing the connection pipe. If the refrigerant pipe is not properly connected and the compressor works with the
CAUTION
service valve open, the pipe inhales the air and it makes the pressure inside of the refrigerant cycle abnormally high.
It may cause explosion and injury.
Mirage_AP50M0@_IBIM_EN_05323A-02.indd 41
90°
Oblique
Outer diameter D (mm)
ø 9.52
ø 19.05
Inclined
Damaged surface
Rough
A (mm)
1.8
2.2
Cracked
Uneven thickness
Burr
Pipe
Reamer
41
2016-05-19 오후 1:27:25