Framing And Finishing - Regency PG33-NG Owners & Installation

Table of Contents

Advertisement

INSTALLATION
Rear Termination
Simpson Dura-Flue Piping
Flex Piping
For Both Simpson & Flex
NOTE: If this is an outside corner, the minimum
distance between the flue and the outside corner
is 6" (15cm) with AstroCap termination cap or 12"
(30cm) with Dura-Flue termination cap.
Vertical Termination or
Vertical Rise with Horizontal
Termination
For Both Simpson & Flex
8

FRAMING AND FINISHING

Simpson Dura-Flue
Minimum Clearances
Top Header
1/2"
dia. Hole through
(13mm)
wall for Dura-Vent
Drywall
1-1/2"
(38mm)
4"
16-1/2"
3"
(102mm)
(419mm)
(76mm)
Opening for gas
Minimum
connection
Flex Pipe
Minimum Clearances
Top Header
1/2"
dia. Hole through
(13mm)
Drywall
1-1/2"
(38mm)
4"
3"
(324mm)
(102mm)
(76mm)
Opening for gas
Minimum
connection
NOTE: If this is an outside corner, the minimum
distance between the flue and the outside corner
is 6" (15cm) with AstroCap termination cap or
12" (30cm) with Dura-Flue termination cap.
1) Determine the total thickness of facing mate-
rial (e.g. drywall plus ceramic tiles) to allow
the finished surface to be flush with the front
of the unit. Total facing thickness can vary
from 1/2" (13mm) to 1-1/4" (32mm) thick.
Install Side Nailing Strips, and Top Facing
10" (254mm)
Support before unit is slipped into position.
See page 9 for assembly details.
2) Frame in the enclosure for the unit with
framing material.
3) For exterior walls, insulate the enclosure to
the same degree as the rest of the house,
apply vapour barrier and drywall, as per lo-
cal installation codes. (Do not insulate the
fireplace itself.)
4) The top of the unit must not be closer than
30" (762mm) to the ceiling.
5) Combustible material may be brought up to
the top and sides of the unit and be covered
with ceramic tiles, bricks, rock or other suit-
able combustible finishing materials.
Note: The unit does not have to be complete-
10" (254mm)
wall for Flex
6) Use steel studs for framing where the
1-1/2" (38mm) clearance from the flue to
combustible material cannot be maintained.
12-3/4"
ly enclosed in a chase. The clearance
on top of the unit is 0" to the standoffs
so combustible building materials can
be laid directly on top of the standoffs.
You must maintain clearance from the
flue to combustible materials for flex
for Simpson Dura-Flue, see page 7.
Regency PG33 Gas Inbuilt