Four Way Valve Abnormality - Daikin FVXS25FV1B Service Manual

Inverter pair floor standing type
Hide thumbs Also See for FVXS25FV1B:
Table of Contents

Advertisement

Troubleshooting
4.13

Four Way Valve Abnormality

4.13.1 25/35 class
EA
Remote
Controller
Display
Method of
The indoor air temperature thermistor, the indoor unit heat exchanger thermistor, the outdoor
temperature thermistor and the outdoor unit heat exchanger thermistor are checked to see if
Malfunction
they function within their normal ranges in the operating mode.
Detection
Malfunction
A following condition continues over 10 minute after operating 5 minutes.
Decision
Conditions
Supposed
Causes
104
Cooling / dry operation
(room temp. – indoor heat exchanger temp.) < –5°C
Heating
(indoor unit heat exchanger temp. – room temp.) < –5°C
Connector in poor contact
Thermistor defective
Outdoor unit PCB defective
Four way valve coil or harness defective
Four way valve defective
Foreign substance mixed in refrigerant
Insufficient gas
SiBE06-708
Service Diagnosis