Capacitor Voltage Check; Power Transistor Check - Daikin FVXS25FV1B Service Manual

Inverter pair floor standing type
Hide thumbs Also See for FVXS25FV1B:
Table of Contents

Advertisement

SiBE06-708
5.1.10

Capacitor Voltage Check

Check No.12
Before this checking, be sure to check the main circuit for short-circuit.
5.1.11

Power Transistor Check

Check No.13
25/35 class
Note:
Check to make sure that the voltage between the terminal of Power transistor (+) and (-) is
approx. 0 volt before checking power transistor.
< Measuring method >
Disconnect the compressor harness connector from the outdoor unit PCB. To disengage the
connector, press the protrusion on the connector.
Then, follow the procedure below to measure resistance between power transistor (+) and (-)
and the U, V and W terminals of the compressor connector with a multi-tester. Evaluate the
measurement results for a pass/fail judgment.
<Power transistor check>
Negative (-) terminal of
tester (positive terminal
(+) for digital tester)
Positive (+) terminal of
tester (negative terminal
(-) for digital tester)
Normal resistance
Unacceptable resistance
Service Diagnosis
Checking the capacitor voltage
With the circuit breaker still on, measure the voltage according to the drawing of the model in
question. Be careful never to touch any live parts.
Multimeter
(DC voltage range)
Compressor lead wire
Fan motor lead wire
Power transistor
Reactor lead wire
Electronic expansion valve
lead wire
UVW
(+)
UVW
Power transistor
(+)
Several kΩ to several MΩ (∗)
Short (0 Ω) or open
OL lead wire
Thermistor lead wire
Reversing solenoid
valve lead wire
(Heat pump type only)
(R5222)
Power transistor
UVW
(-)
UVW
Power transistor
(-)
Check
143