Toshiba Magnia 510D User Manual page 15

Hide thumbs Also See for Magnia 510D:
Table of Contents

Advertisement

Getting Started
Extreme heat, cold, or humidity. Use the server within the following range of ambient
conditions:
Temperature: 50° F to 95° F (10° C to 35° C)
Relative humidity: 30% to 80% RH (no condensation)
If the server is exposed to conditions that could result in condensation accumulating
on the server's cabinet or its internal components, wait one to two hours before
operating the server.
HINT: To inspect the server for moisture, remove the side panel. For instructions on
removing the side panel, see "Removing the side panel" on page 32.
CAUTION: Condensation can corrode server components and short-circuit its
electrical circuits if the unit is on. Avoid exposing the server to condensation during
use and storage.
Allow sufficient space around the server and other equipment to allow for installation and
maintenance.
2 in. (5 cm)
12 in. (30 cm)
Minimum installation clearances
8 in. (20 cm)
2 in. (5 cm)
Environmental considerations
15

Advertisement

Table of Contents
loading

Table of Contents