4.8.8 BASIC ADJUSTMENT MENU
The basic adjustment menu may be used to view and / or alter factorty pre set operating
parameters.
NOTE: Adjustment of any parameters may effect the operation of the Electromax Solar and
should only be carried out by a competent person.
FIGURE 33: BASIC ADJUSTMENT MENU SETTINGS
PARAMETER
DESCRIPTION
0
COLLECTOR PROTECTION ON / OFF
1
COLLECTOR PROTECTION TEMPERATURE START
2
RECOOLING FUNCTION ON / OFF
(ONLY WHEN COLLECTOR PROTECTION IS ON)
3
TEMPERATURE TO WHICH THE STORAGE TANK
IS RECOOLED AFTER ACTIVE COLLECTOR
PROTECTION
4
TIME CONTOLLED CIRCULATION WITH TUBE
COLLECTORS
5
ENERGY PRODUCTIVITY MEASUREMENT ON / OFF
6
GLYCOL TYPE
7
GLYCOL MIX
8
VOLUME FLOW LPM
9
ANTIFREEZING ON / OFF
10
ANTIFREEZE TEMPERATURE START
11
CHOICE OF FUNCTION
12
SYSTEM TYPE
To view a system parameter:
Select the basic adjustment sub menu as shown in section 4.8.4
Press UP or DOWN to scroll to the required parameter.
NOTE: To avoid accidental changes to the parameters within the basic adjustment sub
menu it is only adjustable within one minute of switching the Electromax Solar on. After one
minute access to the basic adjustment sub menu is limited to viewing only.
To alter a system parameter:
Select the basic adjustment sub menu as shown in section 4.8.4
Press UP or DOWN to scroll to the required parameter.
Press RIGHT to select the parameter. The icon will flash.
Press UP to increase the parameter value.
Press DOWN to decrease the parameter value.
Press RIGHT and the OK icon will flash.
Press RIGHT to confirm the parameter setting.
RANGE
FACTORY SET
1 = ON
0 = OFF
0 = OFF
110 - 150°C
120°C
1 = ON
0 = OFF
0 = OFF
30 - 90°C
40°C
1 = ON
0 = OFF
0 = OFF
1 = ON
0 = OFF
0 = OFF
0 - 10
0
0 - 100%
50
0,5 - 25,0
10,0
1 = ON
0
0 = OFF
-20 - +7°C
0
0 - 3
0
0 = SOUTH
0 - 4
3 = EAST/WEST
47