WALL THIMBLE
COVER
WALL THIMBLE
Figure 5.8
Step 5.
Place the wall thimble cover over the pipe assembly and
slide the appliance and vent assembly towards the wall,
carefully inserting the vent pipe into the vent termination
cap assembly. It is important that the vent pipe extend into
the vent termination cap a sufficient distance so as to result
in a minimum pipe overlap of 1-1/4 in. (32mm). Secure the
connection between the vent pipe and the vent termination
cap by attaching the two sheet metal strips extending from
the vent termination cap assembly into the outer wall of
the vent pipe. Use the two sheet metal screws provided to
connect the strips to the pipe section (Figure 5.9).
1/4 in. (6mm)
FOLD STRAP
HERE
SHEET METAL SCREW
WALL THIMBLE COVER/CEILING
FIRESTOP AS REQUIRED BY
LOCAL JURISDICTION
Figure 5.9
Note: The attachment from the vent pipe to the vent
termination cap must be sealed with silicone. Termination
caps shall not be recessed into a wall or siding.
Page 14
VINYL SIDING
APPLY SEALANT
TO ALL FOUR
SIDES
SCREWS
BOLT HORIZONTAL
TOP TO VINYL
STANDOFF
SCREWS
VINYL SIDING
STANDOFF WITH
SIDING BENEATH
REMOVED
WALL
THIMBLE
STRAP
Quadra-Fire • Hudson Bay • 7003-121_R20 • 11/14
!
Fire Hazard.
Exhaust Fume Risk.
Impaired Performance of Appliance.
• Ensure vent components are locked together correctly.
• Pipe may separate if not properly joined.
!
Do NOT connect a pipe section to a termination cap without
using the telescoping flue section found on the termination cap.
!
Burn Risk.
• Local codes may require installation of a cap
shield to prevent anything or anyone from
touching the hot cap.
WARNING
WARNING
WARNING