The Themaclassic F30E boiler is a wall mounted modulating
combination boiler with electronic ignition providing central
heating and instantaneous hot water.
The Themaclassic F30E SB boiler is a wall mounted modulating
boiler with electronic ignition providing central heating.
These boilers are of the I2H category for use with Natural Gas
(G20) as distributed in the United Kingdom.
These boilers have a fan assisted balanced flue which both
discharges the products of combustion to and draws the
combustion air from the outside of the room.
These boilers are suitable for horizontal top and rear outlet flue
connection only and can be fitted with horizontal flue, vertical
flue or twin-pipe flue. Refer to flue options guide for further
information, this is available from your nearest stockist.
The central heating temperature is user adjustable from the
boiler control panel.
The domestic hot water temperature is user adjustable from the
boiler control panel (F30E Only).
Domestic hot water demand always has priority over heating
demand (F30E Only).
The pump, expansion vessel and associated safety devices are
all fitted within the boiler.
These boilers can be installed against either an external wall or
on an adjacent inside wall, that is, the flue system will pass
directly to the rear or to either side to the terminal fitted on the
outside wall face.
The installation must be carried out by a qualified registered
person in accordance with the relevant requirements of The
Building Regulations, The Water Byelaws, The Building
Standards (Scotland) Regulations and any applicable local
regulations.
These instructions should be carefully followed for the safe and
economical use of your boiler.
Electrical Supply
WARNING: This boiler must be earthed.
All system components shall be of an approved type and shall
be connected in accordance with the current issue of BS7671
and any applicable local regulations.
All external wiring between the appliance and the electrical
supply and earthing requirements shall comply with the current
IEE Regulations.
Your Themaclassic F30E or Themaclassic F30E SB boiler
has been factory configured to operate at the heart of an
existing installation. However, because many installations are
specially designed, do not hesitate to contact your installer who
will be able to ensure that you get the best performance from
your installation, by adjusting the heating circuit's maximum
output or temperature.
Once these settings have been made, you can still adjust the
temperature to suit your needs.
Central heating adjustment
The selector switch enables you to vary the temperature of the
water in the central heating circuit from the minimum setting
(approx. 38˚C) up to the maximum temperature (approx. 87˚C)
4000122704-1

Introduction

Connection of the boiler and system controls to the mains
supply must be through a common isolator and must be fused
3A, maximum. This method of connection must be by a fused
double pole isolating switch, with a minimum contact separation
of 3mm on both poles. The switch should be readily accessible
and preferably adjacent to the appliance. It should supply the
appliance only and be easily identifiable as so doing.
Alternatively, an unswitched shuttered socket outlet and 3A
fused 3 pin plug, both to the current issue of BS1363 may be
used provided that they are not used in a room containing a bath
or shower.
Wiring to the boiler must be PVC 85
than 0.75mm
Gas safety (Installation and use) Regulations
In your interests and that of gas safety, it is the law that ALL gas
appliances are installed and serviced by a qualified registered
person in accordance with the above regulations.
Gas leak or fault
If a gas leak or fault exists or is suspected, turn the boiler off and
consult the local gas supply company or your installation/
service company.
Air in the heating system
Persistent air in the heating system may indicate leaks in the
system or corrosion taking place. Call your Installation/Servicing
company.
Overheating safety
In the event of a problem, the overheating safety devices cause
safety shutdown of the boiler. If this happens, call your
Installation/Servicing company.
Boiler controls
The control panel, located at the lower front of the boiler casing,
see diagram 1, allows the boiler to be started, shut down,
controlled and monitored during use.
Flue
Do not obstruct the outside terminal of the flue.
Ancillary equipment
A range of flue accessories are available including vertical
flues, twin-pipe flues, bends etc.
For further information contact your supplier.

Controls and lighting

set by your installer. Most of the time, the mid position will meet
your needs but the selector should be moved nearer to the
maximum setting in very cold weather when your home is not
reaching the required temperature.
Domestic hot water (F30E Only)
The selector switch can be adjusted from a temperature of
(approx. 34˚C up to 65˚C) or more.
The ECO setting is ideally suited for all the requirements of
normal family use (showers, washing up etc.). The maximum
setting should be reserved for occasional use when very hot
water is required.
4
o
C insulated cable, not less
2
(24/0.20mm).