Hp 1200 W Common Slot Platinum Plus Hot-Plug Power Supply (94% Efficiency); Hp 1500W Common Slot -48Vdc Hot-Plug Power Supply - HP ProLiant DL580 User Manual

Gen9
Hide thumbs Also See for ProLiant DL580:
Table of Contents

Advertisement

HP 1200 W Common Slot Platinum Plus Hot-Plug Power Supply
(94% efficiency)
Specification
Input requirements
Rated input voltage
Rated input frequency
Rated input current
Maximum rated input power
BTUs per hour
Power supply output
Power supply output
Rated steady-state power
Maximum peak power

HP 1500W Common Slot -48VDC Hot-plug Power Supply

Specification
Input requirements
Rated input voltage
Rated input current
Rated input power (W)
Rated input power (BTUs per
hour)
Power supply output
Rated steady-state power (W)
Value
100 VAC,110 to 120 VAC, 200
to 240 VAC
50 Hz to 60 Hz
9.3 A at 100 VAC
9.5 A at 110 to 120 VAC
6.6A at 200 to 240 VAC
1000 W at 120V AC input
1320 W at 230V AC input
3408 at 120V AC input
4500 at 230V AC input
800W at 100V AC input (low line)
900W at 108V to 132V AC input
(low line)
1200 W at 200V to 240V AC
input (High line)
800 W at 100V AC input
900 W at 120V AC input
1200 W at 200V to 240V AC
input
800 W at 100V AC input
900 W at 120V AC input
1200 W at 200V to 240V AC
input
Value
-40 VDC to -72 VDC
42 A at -40 VDC input
33.5 A at -48 VDC input
22.2 A at -72 VDC input
1621 W at -40 VDC input
1607 W at -48 VDC input, nominal
input
1598 W at -72 VDC input
5530 at -40 VDC input
5484 at -48 VDC input
5451 at -72 VDC input
1500 W at -40 VDC to -72 VDC
Specifications 113