en | System Overview
Mode
1
2
3
Operate in mode 1 and 3 only, when connected to LSN detectors.
1.
2.
Notice!
Malfunction
The cable length between the detector and the remote indicator must not exceed 3 m when
connected by an unshielded cable.
Technical specifications
Operating Voltage
Maximum current
consumption
Permissible wire gauge
Display medium
Dimensions
Weight
2014.11 | 1.1 | F.01U.283.550
Terminal connection
+
+
+
Place the cap on the base plate in such a way that the two hooks are inserted into the
slits.
Press the cap lightly onto the base plate until the snap‑fit‑hook engages.
Alarm condition
The remote indicator shows steady red light. Current has
to be limited to max. 30 mA.
The remote indicator shows steady red light. Input voltage
range: 8.5 V DC ... 33 V DC. Constant current consumption
13 mA.
The remote indicator shows flashing red light. Input voltage
range: 11 V DC ... 33 V DC. Constant current consumption
3 mA.
FAA‑420‑RI‑ROW
5 ‑ 30 V DC
20 mA
0,6 – 2 mm
1 LED
85 x 85 x 28 mm
45 g
Operation Guide
AVENAR detector 4000
FAA‑420‑RI‑DIN
9 ‑ 30 V DC
Mode 1: limited to 30 mA
Mode 2: 13 mA
Mode 3 : 3 mA
0,6 ‑ 0,8 mm
2 LED
85 x 85 x 35 mm
65 g