Sell Status; Table 13 Sell Status Messages - Outback FXR2012A Operator's Manual

Fxr series inverter/charger
Table of Contents

Advertisement

Troubleshooting

Sell Status

Sell Status messages describe conditions relating to the inverter's grid-interactive mode. This screen is
viewed using the MATE3 Home screen's soft keys. (See the MATE3 manual for more instructions.) One
or more messages will display Y (yes). If a message says N (no), it is not the cause of the disconnection.
If the inverter has stopped selling or charging unexpectedly, this screen may identify the reason. More
often these messages are used by a normally functioning inverter to identify external conditions that
are preventing selling or charging. (If nothing has stopped, the messages will indicate that as well.)
The acceptable limits for AC source voltage and frequency are controlled by the Grid Interface
Protection settings, which are shown in the default menus beginning on page 76. If the AC source
exceeds these limits, the inverter will stop selling and display the appropriate code. (At the same time
it will disconnect from the utility grid, with an appropriate message as shown in Table 12 on page 65.)
After the source returns to the acceptable range, the screen will begin its reconnection timer (with a
default setting of five minutes). When the timer expires, the inverter will reconnect to the utility grid
and begin selling power again.
If the AC source is unstable, it may become unacceptable before the timer expires. This may cause the
timer to continually reset. It is possible for brief fluctuations to occur that are too fast to be seen on a
DVM. If this happens, the appropriate message will still appear on the system display for a short time
to help troubleshoot the problem.
Additionally, undersized wires or bad connections can result in local voltage problems. If a Voltage
Too Low or Voltage Too High message is accompanied by voltage changes that do not appear at the
main utility connection, check the wiring.
Sell Status
Selling Disabled
Qualifying Grid
Frequency Too Low
Frequency Too High
Voltage Too Low
Voltage Too High
Battery < Target
66
Table 13
Sell Status Messages
Definition
The Grid-Tie Enable command has been set to N (no).
All utility grid conditions are acceptable. The inverter is running
a timed test during which it confirms the grid quality. The timer
is shown on the screen. At the end of that time, the inverter
may be ready to sell.
The utility grid's AC frequency is below the acceptable range
for selling.
The utility grid's AC frequency is above the acceptable range
for selling.
The utility grid's AC voltage is below the acceptable range
for selling.
The utility grid's AC voltage is above the acceptable range
for selling.
The battery voltage is below the target voltage for that stage
(Float, Selling, etc.). No excess energy is available to sell.
900-0167-01-00 Rev A