Power Save; Figure 16 Power Save Levels And Loads - Outback FXR2012A Operator's Manual

Fxr series inverter/charger
Table of Contents

Advertisement

Power Save

Each FXR inverter consumes 34 watts of idle power while it remains on, even if it is not actively
inverting or charging. The Power Save function allows the option to put part of a parallel system into
a quiescent state known as Silent mode. This mode minimizes the idle consumption. The inverters
will come on again when the loads require power. (The term "Silent" is also used in an unrelated
context during battery charging. See page 36.)
When the load increases by 12 Aac, the master inverter activates an additional slave inverter for assistance.
When the load decreases to 4 Aac or less (as detected by the master), the slave is deactivated and returns to
Silent mode. Each additional load increments of 12 Aac activates an additional slave.
The order in which slaves activate (or return to Silent mode) is controlled by programming in the system
display. The inverters are given a "rank", or level number. Lower rank numbers activate when lesser loads
are applied. Higher ranks only activate when the load increases to a high level.
The lowest-ranked inverters do not enter Silent mode. This includes the master and subphase masters.
They remain active unless specifically turned off. These inverters can still enter Search mode.
Minimal load
Increasing load
High load
Maximum load
The actual watt and ampere thresholds for activating each model are depicted on the following pages.
IMPORTANT:
It is highly recommended to use the MATE3 Configuration Wizard to set up this function. It is
essential to set the slave Power Save Levels in sequential order. Failure to set them up correctly will
cause erratic system performance. The Configuration Wizard automatically programs the correct
priorities. (See the MATE3 owner's manual.)
To set these items manually without the Configuration Wizard:
In the MATE3 system display, the Power Save Ranking screen uses Power Save Level selections to
assign ranks to the inverter on each port. The screen reads Master Power Save Level or Slave Power
Save Level, depending on the inverter's stacking designation.
The stacking designations also control which ports are used on the HUB10.3 communications
manager. The master inverter must be plugged into port 1. In parallel stacking, any slave inverter can
use any other port, beginning with port 2. In series or three-phase stacking, the port assignments are
very specific. They are also different from each other, as illustrated in the HUB10.3 literature.
900-0167-01-00 Rev A
Master
Slave 1
On
On
On
On
Figure 16
Power Save Levels and Loads
Slave 2
Off
Off
On
Off
On
On
On
On
Operation
Slave 3
Off
Off
Off
On
47