Outback FXR2012A Operator's Manual page 38

Fxr series inverter/charger
Table of Contents

Advertisement

Operation
Voltage
Absorption
Absorption
Set Point
Float
Set Point
Re-Float
Set Point
Absorption
timer runs
Time
Inverter now charging to a new set point
Inverter has reached the charging set point
Figure 8
Example of Multiple Cycles
In Figure 8 (Cycle 1), the charger initially completes Absorption. When the Absorption timer expires, the
charger goes Silent until battery voltage decreases to the Re-Float setting. The Float timer is reset to its
maximum. The charger proceeds through Refloat and Float until it is interrupted by a loss of AC power.
Cycle 2 begins when the AC source is restored. During the AC loss, the battery voltage did not decrease to
the Re-Float setting, so Float Time retains the remainder of the previous cycle. The charger returns to
Refloat and proceeds through the Float stage. Cycle 2 completes the Float stage when its timer expires. It
then goes Silent.
Note that in Cycle 1, Absorb Time had expired. It was not reset afterward and retained a "remaining run
time" of zero. The Bulk and Absorb stages do not occur on subsequent cycles until the timer reads
something other than zero.
This graph is continued in Figure 9. During the Silent period AC is lost again. The battery voltage decreases
until it reaches the Re-Bulk set point. This causes the charger to prepare a new three-stage cycle from the
beginning, but it cannot do so until the AC source is restored.
38
Cycle 1
Silent
Refloat
Float
Float timer
Float timer runs (part)
resets
Inverter completed charging; the previous set point is no longer in use
Inverter waiting to charge when AC restored; the previous set point is still in use
Repeated Charging (1
Cycle 2
AC Loss
AC Loss
Refloat
Float
Float timer runs
st
and 2
nd
Cycles)
Silent
900-0167-01-00 Rev A

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vfxr2812aVfxr3524aFxr2524aVfxr3648aFxr3048a