Table 5 Aux Mode Functions - Outback FXR2012A Operator's Manual

Fxr series inverter/charger
Table of Contents

Advertisement

Operation
When battery voltage rises above a settable high voltage level, the AUX output is activated after a
settable delay. The AUX output controls a larger relay, which allows current to flow from the batteries
to a dedicated AC load when energized. Diversion is usually used to regulate battery charging. The AC
device is usually wired to the output or load panel and must be left on. It must be sized to dissipate all
of the energy from the renewable source if necessary. Diversion will turn off following a delay when a
low DC voltage setting is reached.
The AUX output will automatically turn on to run the loads if the inverter accepts an AC source.
Settable parameters include:
Low and high DC voltage
On and off delay
During variable conditions, the AUX output is triggered no more than once per minute (if voltage
conditions are still met). This prevents rapid nuisance cycling of the AC load.
AC Divert should not be used as the sole source of battery regulation. If the inverter shuts down or fails,
the batteries could suffer severe damage. This function should be supported by an external regulator.
If the inverter shuts down due to overload, the AUX output will also shut down. If the inverter
load exceeds 30 Aac, the AUX output will turn off to prevent an overload condition.
If either the FETs or the capacitors (see page 64) become too hot, the AUX will turn off due to
diminished inverter wattage capacity.
Note that even if every function in the menu is set to Off, external programming from other devices
may still activate the AUX output. An example is the system display's AGS function. See page 53.
The AUX functions are summarized in Table 5.
Name
Purpose
Load
Operates designated loads
normally; turns off loads in
Shed
severe conditions
Gen Alert
Starts generator to charge
batteries
Fault
Signals that the inverter shut
down due to error
Runs fan to vent batteries
Vent Fan
while charging
Runs fan to cool inverter
Cool Fan
DC Divert Turns on DC dump load to
prevent overcharging
Signals disconnect of grid-tied
GT Limits
inverter due to AC conditions
Source
Signals that the inverter
accepted an AC source
Status
AC Divert
Turns on AC dump load to
prevent overcharging
52
Table 5
Aux Mode Functions
Start
High Vdc
Low Vdc
Error present
High Vdc
Internal sensor > 60°C
High Vdc
GIP parameters
not met
AC source accepted
High Vdc
AC source accepted
Triggers
Stop
Low Vdc
High temp
Low output Vac
High input Aac
High Vdc
Error cleared
Below high Vdc
Internal sensor < 49°C
Low Vdc
GIP parameters met
AC source
disconnected
Low Vdc
High output load
High temperature
Settable
Points
Low & high Vdc
On & Off delay
Low & high Vdc
On & Off delay
None
High Vdc
Off delay
None
Low & high Vdc
On & Off delay
None
None
Low & high Vdc
On & Off delay
900-0167-01-00 Rev A