Grid Use Time

The inverter system is capable of connecting to, or disconnecting from, the utility grid based on time
of day. It can also be programmed to connect at different times on weekdays and on weekends.

Load Grid Transfer

The inverter system is capable of connecting to, or disconnecting from, the utility grid based on load
size. This avoids undesirable battery discharge from excessive loads. It can also be programmed to
connect to the grid when the batteries reach a low voltage due to excessive discharge.
Complete Grid
Mode
Recharge
Mini Grid
Yes
HBX
No
Grid Use
Depending on
Time
Duration
Load Grid
Depending on
Transfer
Duration
54
Table 6
Comparison of Grid Functions
System
Connects
Display
to Grid
Required
Low
initial setup
Battery
only
Remains
Low
installed
Battery
Remains
Time of
installed
Day
Remains
High Load
installed
Renewable
Adjustability
Energy
Limited (many
Must be larger
settings are
than inverter
automatic)
Preferred to be
Full
larger than
inverter
Full
Not required
Full
Not required
Location of
Function
Inverter
System
System
System