Emerson Liebert GXT4 User Manual page 62

Hide thumbs Also See for Liebert GXT4:
Table of Contents

Advertisement

Table 21
Battery run time, minutes
Number of External
Battery Cabinets
Internal Battery
+ 4 External
Battery Cabinets
Internal Battery
+ 5 External
Battery Cabinets
Internal Battery
+ 6 External
Battery Cabinets
Run times in this table are approximate. They are based on new, fully charged standard battery modules at a temperature of 77°F (25°C)
with 100% resistive UPS loading. Run times listed above can vary by ±5% due to manufacturing variances of the individual batteries.
Using the configuration program, the user may specify the number of external battery cabinets
attached to the UPS. The factory default is programmed for internal batteries only.
Table 21 shows the estimated run times at different loads.
®
Liebert
GXT4
Load Percent
of Capacity
5 kVA
10%
454
20%
323
30%
194
40%
153
50%
134
60%
110
70%
95
80%
77
90%
67
100%
53
10%
464
20%
343
30%
224
40%
166
50%
150
60%
134
70%
112
80%
100
90%
82
100%
74
10%
480
20%
430
30%
317
40%
204
50%
162
60%
148
70%
134
80%
120
90%
103
100%
92
56
208/120 VAC RT Models
6 kVA
8 kVA
10 kVA
442
463
300
340
161
218
138
164
110
147
92
130
74
109
62
96
50
79
46
71
454
480
324
429
194
316
153
203
134
161
110
147
95
133
77
113
67
102
53
91
463
480
341
442
219
334
164
227
148
191
131
159
110
147
97
135
80
122
71
107
Specifications
208 VAC RT Model
6 kVA (L630)
447
456
310
420
165
304
144
200
122
160
99
145
79
130
68
111
53
102
49
93
459
466
332
430
206
332
158
225
140
195
122
161
102
149
82
137
73
126
64
110
467
480
420
452
301
423
183
321
153
227
138
195
122
162
104
152
92
142
77
133