Commissioning, inspection, maintenance
Further details regarding the individual steps
4. Insert and secure new burner gauze
assembly D with new gasket E.
!
Please note
Fasten screws tightly enough
to ensure the components are
not being damaged and are
functioning correctly.
5. Mount thermal insulation ring C.
!
Please note
Fasten screws tightly enough
to ensure the components are
not being damaged and are
functioning correctly.
Checking and adjusting electrode
40
4
+0,5
(cont.)
6. Fit electrode B.
!
Please note
Fasten screws tightly enough
to ensure the components are
not being damaged and are
functioning correctly.
1. Check the electrode for wear and
contamination.
2. Clean the electrode with a small
brush (not with a wire brush) or emery
paper.
3. Check the electrode gaps. If the gaps
are not as specified or the electrode
is damaged, replace and align the
electrode together with a new gasket.
Tighten electrode fixing screws.
!
Please note
Fasten screws tightly enough
to ensure the components are
not being damaged and are
functioning correctly.