Viessmann VITODENS 100-W Installation And Service Instructions Manual page 62

Wall mounted gas condensing boiler natural gas and lpg version
Hide thumbs Also See for VITODENS 100-W:
Table of Contents

Advertisement

Gas type conversion
Converting from LPG to natural gas
Changing the gas type at the control unit
r
r
Checking the CO
See page 36.
62
r
content
2
(cont.)
1. Turn on the ON/OFF switch.
2. Turn both rotary selectors "tw" and
"tr" simultaneously into their
respective central positions.
"SERV" appears on the display.
3. Turn rotary selector "tr" within 2 s
fully anticlockwise.
The set value and "A" flash on the
display.
4. Change the control unit to natural gas
or LPG by turning rotary selector
"tw".
The display shows:
■ "0" for operation with natural gas
or
■ "1" for operation with LPG.
5. The set operating mode is saved
when the value stops flashing, and
the control unit returns to standard
mode.

Hide quick links:

Advertisement

Table of Contents
loading