Communication loss
time
CD72
Set communication loss time. When communication loss time over
CD72 setting, Inverter will active as CD76 selected.
Note : This function does not effect in standby condition.
Communication
error counter
CD73
When communication error continuous time more than CD73 setting.
Inverter will active as CD76 selected.

Address setting

CD74
Each drive must have unique identified addrss if they are controlled by
RS485 communication. Each address connot be duplicated.
0 : broadcast to all inverter.

Transmission speed

CD75
Setting the transmission speed between computer and drive.
0 : 2400 bits/second.
1 : 4800 bits/second.
2 : 9600 bits/second.
3 : 19200 bits/second.
Setting Range
Default Value
Setting Range
Default Value
Setting Range
Default Value
Setting Range
Default Value
52
0.1 ~ 100.0SEC
0.5SEC
0 ~ 10
3
1 ~ 255
1
0 ~ 3
0