Timer unit selector

CD64
0 : hr.min
1 : min.sec
Note 1 : CD64 cannot be reset to default value by CD52. Set CD64 as
needs separately.
Note 2 : In RS485 communication input, CD59~CD63 need to tranfer
minimum unit. Ex CD64=0, CD59=2.3 CD59 contant for
RS485 communication is 2 ¡Ñ 60+30=150(0096H).

Stall prevention

CD65
0 : Disable
1 : Enable
When enable CD65, if any overload over CD66 setting value during
DEC period, inverter will increase DEC time to prevent inverter to go
into fail safe mode.
Overload current
stall prevention
CD66
During ACC, if ACC time is too
short or load is too heavy, the
current will reach CD66 value,
inverter will stop to ACC until
current is lower than CD66
value.
Actual stall current limit=rate current ¡Ñ CD66 percentage. Rate current
number refers to section 2 table.
Setting Range
Default Value
Setting Range
Default Value
Setting Range
Default Value
CD66
Constant frequency
50
0 ~ 1
0
0 ~ 1
0
20 ~ 250%
170%
Current
Output HZ
Time