Heat pump, Split, single service
Line
Function
1014 U
Frost-free ambient temperature setpoint
1016 S
Maximum comfort setpoint
1020 I
Heating curve slope
1021 I
Off-set of the heating curve
1026 S
Adaptation of the heating curve (see § 3.3.2)
1030 I
Summer/Winter heating limits
When the average of the outside temperatures over the past 24 hours reaches 18°C, the regulator switches off the
heating (as an economy measure).
During summer mode, the display shows "Eco".
This function is only active in automatic mode.
1032 S
Limit of daily heating
This function enables you partially to offset the automatic summer/winter switchover during the intermediate seasons.
Increasing the value delays the switchover to summer regime.
Decreasing the value advances the switchover to summer regime.
This function is only active in automatic mode.
1050 I
Influence of the ambient temperature
If the installation is fitted with a room thermostat:
This function enables you to choose the ambient temperature's influence on the setting.
If no value is entered, the setting is made based on the temperature control.
If the parameter is set at 100%, the setting is only based on the ambient temperature.
1090 S
Maximum optimisation on switch-on
1091 S
Maximum optimisation on switch-off
1100 S
Start of increase in reduced functioning mode
1101 S
End of increase in reduced functioning mode
1130 S
Mixer valve increase
1132 S
Type of servomotor
1133 S
Switching differential 2-pos
1134 S
Servomotor travel time
1150 I
Floor controlled drying (fig. 44)
– off: Early interruption of the current programme, programme inactive
– Operational heating
– Heating ready for occupation
– Operational heating + ready heating
– Ready heating + operational heating
– Manual
Manual mode enables you to programme your own concrete slab drying time.The function ends automatically after
25 days.
1151 I
Manual floor drying setpoint
(if line 850 = manual)
This function enables you to set the custom concrete slab drying temperature. This temperature remains fixed. The
concrete slab-drying programme stops automatically after running for 25 days.
1156 I
Current drying day
1157 I
Terminated drying days
1161 S
Excess heat evacuation
Installation and operating manual "1350-EN"
Setting range
or display
from 4°C... to reduced
temperature
20...35 °C
0.1... 4
-4.50 °C... 4.5 °C
off, ON
8 °C ... 30 °C
-10 °C ... 10 °C
1%... 100%
0 ... 360 min
0 ... 360 min
- 30 ... 10 °C, --- °C
- 30 ... 10 °C, --- °C
0 ... 50 °C
2-pos, 3-pos
0 ... 20 °C
30 ... 873 s
0 °C... 95°C
0 ... 32
0 ... 32
off, Heating regime,
Permanent
Setting
Basic
setting
increment
0,5 °C
8 °C
1 °C
28 °C
0,02
0.5
0,5 °C
0 °C
off
0,5 °C
18 °C
1 °C
-3 °C
1%
20%
10 min
120 min
10 min
120 min
1 °C
---
1 °C
- 5 °C
1 °C
0 °C
3-pos
0,5 °C
2 °C
1 s
240 s
off
1 °C
25 °C
Permanent
39