3.1.2 Locking and releasing the key pad
and
for 3 seconds:
Press
3.2 Starting the device
check that no tools or other objects have been left inside the device,
the access door for technical components must be fitted,
set the by‐pass and setting valves (see § 2.4) as follows:
- valve 1 completely open,
- valves 2‐3‐4 & 5 closed.
An incorrect setting of the by‐pass valve may lead to device malfunction
switch on the filter system,
progressively close valve 1 in order to increase the filter pressure to 150 g (0.150 bar) ,
open valves 2, 3 and 4 completely, then half open valve 5 (see §2.4) (the air accumulated in the heat pump
condenser and in the filter circuit is then bled),
If valves 4 and 5 are not fitted, open valve 1 completely, and half close valve 3.
power‐up the heat pump,
if the heat pump is on stand‐by:
for 2 seconds, and
and set‐point temperatures will be displayed:
set the required water temperature:
to increase temperature,
- press
to decrease temperature,
- press
When the pool reaches the required temperature, the heat pump will automatically stop.
set the water flow‐rate using the menu , when the indicator
flow‐rate status:
Status
water flow‐rate ok
Display
set the flow‐rate using valve 5 (or 3 if no valve 5 is fitted), and, to quit the menu, press
During this adjustment phase, wait for a few minutes after each change in valve position to allow the
device to balance.
3.3 Checks to perform after start‐up
The heat pump must stop when:
the set‐point temperature is lowered using the digital control panel,
filtering is stopped or valve 2 or 3 is closed 3,
the digital control panel is turned off by pressing
H0439100.A1.EN – 2013/10
(die Softnummer hängt von dem Modell ab) for 3 seconds, and the water
no water flow
or
for 3 seconds,
, press on
, a 2‐minute delay will start,
is steady: press
water flow‐rate too weak
,
will appear
to display the water
water flow‐rate too strong
.
8