Disposing of condensation:
Warning: your device can produce several litres of water per day. It is strongly recommended to guide the
flow to drains.
connect a Ø18 interior pipe (not supplied), to the grooved end‐piece mounted on the base of the
appliance,
outlet: to the back or on the side:
2.5 Electrical connections
2.5.1 Voltage and protection
the electrical supply to the heat pump must include a protection and circuit‐breaker device (not supplied)
complying with the standards and regulations in force in the country,
additional protection may be required during installation to protect against overvoltage category II,
the device is designed for connection to a general power grid with TT and TN.S grounding systems,
electrical protection: circuit‐breaker (curve D) or fuse (Am) (see § 2.5.3 for ratings), and with a 30 mA dedicated
differential trip switch (circuit‐breaker or switch).
electrical conduits must be secured,
tolerance for voltage variation: ± 6% (during operation),
use cable suitable for outdoor use, type RO2V or equivalent in countries outside of the European
community, with an outer diameter between 9 and 18 mm,
use the cable gland to run the supply cable into the device.
2.5.2 Connections
the electrical supply cable must not be exposed to elements that are sharp, hot or at risk of being crushed,
check that all cables are secure and all terminal connections are correct.
Loose terminals may cause the supply terminal board to overheat and will void the warranty.
The device must be connected to the earth (grounded)
Risk of electric shock inside the device
The device must only be commissioned by a qualified and experienced technician
If the power cable is damaged, it must be replaced by a qualified technician
Single‐phase
phase (L) + neutral (N) + Earth (PE)
2.5.3 Cable cross‐sections
•supply cable cross‐section: cables with a maximum length of 20 metres (calculation base: 5A/mm²), must be
checked and adapted depending on installation conditions.
Z300
Voltage
M4
230V‐50Hz
M6‐MD6
230V‐50Hz
T6‐TD6
400V‐50Hz
M7
230V‐50Hz
MD8
230V‐50Hz
TD8
400V‐50Hz
H0439100.A1.EN – 2013/10
Maximum I input
A
10
14.5
5
16.1
22
9.4
Three‐phase
phases (L1 + L2 + L3) + neutral (N)
Cable cross‐section
mm²
3 x 2.5
3G2.5
3 x 2.5
3G2.5
5 x 2.5
5G2.5
3 x 4
3G4
3 x 6
3G6
5 x 2.5
5G2.5
+ Earth (PE)
Electrical protection
A
16
16
10
20
25
10
5