Disposing of condensation: 
Warning: your device can produce several litres of water per day. It is strongly recommended to guide the 
flow to drains. 
 connect  a  Ø18  interior  pipe  (not  supplied),  to  the  grooved  end‐piece  mounted  on  the  base  of  the 
appliance,  
 
 outlet: to the back or on the side: 
 
2.5 Electrical connections  
 
2.5.1 Voltage and protection 
 
 the  electrical  supply  to  the  heat  pump  must  include  a  protection  and  circuit‐breaker  device  (not  supplied) 
complying with the standards and regulations in force in the country, 
 additional protection may be required during installation to protect against overvoltage category II,  
 the device is designed for connection to a general power grid with TT and TN.S grounding systems,  
 electrical protection: circuit‐breaker (curve D) or fuse (Am) (see § 2.5.3 for ratings), and with a 30 mA dedicated 
differential trip switch (circuit‐breaker or switch). 
 
 electrical conduits must be secured, 
 tolerance for voltage variation: ± 6% (during operation),  
 use  cable  suitable  for  outdoor  use,  type  RO2V  or  equivalent  in  countries  outside  of  the  European 
 
community, with an outer diameter between 9 and 18 mm, 
 use the cable gland to run the supply cable into the device. 
 
2.5.2 Connections 
 
 the electrical supply cable must not be exposed to elements that are sharp, hot or at risk of being crushed,  
 check that all cables are secure and all terminal connections are correct. 
 
Loose terminals may cause the supply terminal board to overheat and will void the warranty. 
The device must be connected to the earth (grounded) 
Risk of electric shock inside the device  
 
The device must only be commissioned by a qualified and experienced technician 
If the power cable is damaged, it must be replaced by a qualified technician 
 
Single‐phase  
 
phase (L) + neutral (N) + Earth (PE) 
 
 
2.5.3 Cable cross‐sections 
 
•supply  cable  cross‐section:  cables  with  a  maximum  length  of  20  metres  (calculation  base:  5A/mm²),  must  be 
checked and adapted depending on installation conditions.
 
Z300 
Voltage 
M4 
230V‐50Hz 
M6‐MD6 
230V‐50Hz 
T6‐TD6 
400V‐50Hz 
M7 
230V‐50Hz 
MD8 
230V‐50Hz 
TD8 
400V‐50Hz 
 
H0439100.A1.EN – 2013/10
Maximum I input 
10 
14.5 
16.1 
22 
9.4 
 
 
Three‐phase 
phases (L1 + L2 + L3) + neutral (N) 
 
  
Cable cross‐section 
mm² 
 
3 x 2.5  
3G2.5 
3 x 2.5  
3G2.5 
5 x 2.5 
5G2.5 
3 x 4 
3G4 
3 x 6  
3G6 
5 x 2.5 
5G2.5 
 
+ Earth (PE) 
Electrical protection 
16 
16 
10 
20 
25 
10 