Powerful Mode Operation; Economy Mode Operation - Panasonic CS-V18BKP Service Manual

Room air conditioner
Hide thumbs Also See for CS-V18BKP:
Table of Contents

Advertisement

CS-V18B KP CU-V18BK P5 / CS-V24BK P CU-V24B KP5
8.5.
Sleep Mode Auto Operation
Cooling or Soft Dry Operation
Purpose is to obtain a comfortable room temperature while
sleeping. When you press the SLEEP Mode, the following
movement will start to avoid overcooling.
• Sleep shift operation starts, when the room temperature
reaches the setting temperature or after 1 hour of operation.
• The setting temperature will be risen by 0.5°C at the start of
operation and by 0.5°C one hour later.
• The airflow volume will automatically change to Low fan
speed.
• Sleep Mode operation time is 8 hours, the operation will be
stop after 8 hours.
• When used together with the Timer, the Timer has priority.
8.6.

Powerful Mode Operation

• Purpose of this operation is to obtain the setting temperature quickly.
• When the Powerful Mode is set, the set temperature will be automatically decreased 3°C against the present setting
temperature (Lower temperature: 16°C).
• This operation automatically will be running under SHi Fan Speed (Cooling), SLo Fan Speed (Soft Dry).
• Vertical Airflow Direction:-
- In "Manual" setting, the vane will automatically swing down 10° lower than previous setting.
- In "Auto" setting, the vane will automatically swing up and down. However the lower limit will be shifted 10° downward.
• Powerful Mode will operate for 15 minutes only, after that it will shift back to previous operation mode.
• Powerful Mode will stop if:-
- Powerful mode button is pressed again.
- Stopped by ON / OFF switch.
- Timer OFF activates.
- Economy mode button is pressed.
- Sleep mode is pressed.
- Operation mode button is changed.
8.7.

Economy Mode Operation

• Purpose of this operation is to save or reduced electrical power consumption of the room air conditioner.
• When the Economy Mode is set, the set temperature will be automatically increased 0.5°C against the preset setting
temperature (Higher temperature: 30°C).
• This operation automatically will be running under SLo Fan Speed.
• Vertical Airflow Direction:-
In "Manual" or "Auto" setting, the vane will automatically change to Auto Air Swing.
• Economy Mode will stop if:-
- Economy Mode button is pressed again.
- Stopped by ON / OFF switch.
- Timer OFF activates.
- Powerful mode button is pressed.
- Auto or Manual air swing button is pressed.
- Fan Speed control button is pressed.
- Sleep Mode button is pressed ON.
- Operation Mode is changed.