8.8.
Random Auto Restart Control
• If there is a power failure, operation will be automatically restarted after 3 to 4 minutes when the power is resumed.
It will start with previous operation mode and airflow direction.
• Restart time is decided randomly using 4 parameter:-
Intake air temperature, setting temperature, fan speed and Air Swing Blade position.
• Auto Restart Control is not available when Timer or Sleep Mode is set.
• This control can be omitted by open the circuit of JX2. (Refer Circuit Diagram)
8.9.
Indoor Fan Speed Control
• Auto Fan Speed Control
When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table.
• Manual Fan Speed Control
Basic fan speed adjustment (3 settings, from Lo to Hi) can be carried out by using the Fan Speed selection button at the remote
control.
21
CS-V18B KP CU-V18BK P5 / CS-V24BK P CU-V24B KP5