3.06 Connecting Single-Phase Input Power to 320SP or 400SP or 500SP

Installation must meet all National and Local Codes - have only qualified persons make this instal-
lation.
Disconnect and lockout/tagout input power before connecting input conductors from unit.
Always connect green or green/yellow conductor to supply grounding terminal first, and never to a
line terminal.
Make input power connections to the welding power source first.
Input Mains Voltage (50/60 Hz)
Max Recommended Circuit Breaker or Time-Delay Fuse
Max Recommended Standard Normal Operating Fuse
Min Input Conductor Size
Min Input Conductor Size
Suggested Input Cord Type
Input Mains Voltage (50/60 Hz)
Max Recommended Circuit Breaker or Time-Delay Fuse
Max Recommended Standard Normal Operating Fuse
Min Input Conductor Size
Min Input Conductor Size
Suggested Input Cord Type
Ground
Terminal
Art: A-07859
March 16, 2007
POWERMASTER 320SP, 400SP, 500SP
!
WARNINGS
V
208
A
100
A
110
AWG
4
AWG
6
Carolprene® Jacketed Type SOOW 90°C 600 Volt
GND/PE
Ground
Conductor
Line
Disconnect
Switch
Line Fuse
Primary Power Cable
Single-Phase
320SP
V
208
230
400
460
A
70
60
40
A
90
70
45
AWG
6
6
10
AWG
8
8
10
Carolprene® Jacketed Type
SOOW 90°C 600 Volt
UL/CSA Portable Cord
Single-Phase
Single-Phase
400SP
230
400
460
208
230
90
50
45
100
100
60
55
110
100
4
8
10
4
6
8
10
6
UL/CSA Portable Cord
35
40
12
12
500SP
400
460
90
50
45
60
55
4
8
10
6
8
10
3-5