REMEHA P 520-13 Technical Instructions page 16

Fuel oil/gas boilers
Hide thumbs Also See for P 520-13:
Table of Contents

Advertisement

- Unscrew the 8 closing nuts and open the furnace door.
These 3 screws must not be unfastened in any event.
- Remove the lower rear panels.
- Remove the lower rear crosspiece.
- Remove the lower insulating material on the rear.
16
- Brush out the inside of the furnace.
- Clean the soot accumulated in the furnace and lower flue ways
with a vacuum cleaner.
- Close the lower sweeping doors.
- Put back the front casing panels by reversing the removal
procedure.
- Unfasten the wing nuts and remove the lower left and right-hand
sweeping doors.
- Remove any soot deposit with a scraper or a vacuum cleaner.
- Open the lower sweeping cover of the flue gas box (2 H 10 nuts +
Ø 10 washers).
- Remove the soot.
- Put back the sweeping cover and doors.
- Put back the lower insulating material, the crosspiece and panels
by reversing the removal procedure.
Remeha P 520
29/08/05 - 300003791-001-B