- Remove the baffle plates from the upper flue ways.
- Carefully sweep the four flue ways with the brush supplied for that
purpose.
- Brush the baffle plates as well.
- If possible, use a vacuum cleaner.
- Unfasten the nuts up to the stop.
- Push in the handles of the sweeping covers.
- Remove the sweeping covers.
29/08/05 - 300003791-001-B
- Remove the left and right-hand casing covers.
- Remove the top insulating material.
- Brush the vertical plates.
- Put back the sweeping covers, insulating material and casing
covers by reversing the procedure above.
Comments : chemical sweeping is recommended for such
boilers.
- Put the baffle plates back in place. Interlock them with each other
while fitting them into the flue ways.
- Close the upper sweeping doors.
Remeha P 520
15