Boiler performance
The symptom is reduced performance of the pump effect or the boiler effect. The symptom of reduced boiler effect is a
lower water outlet temperature than the set value. The possible causes for this are as follows:
Fault
Scale deposits in boiler tube:
Scale formation acts as insulation and
reduces heat transfer to the water.
The result is raised flue gastemperature
= increased flue gas loss.
Sooted boiler tube:
Soot has the same effect as scale depo-
sits, i.e. that they are both insulating
against the heat transfer to the water
and results in increased flue gas tempe-
rature = increased flue gas loss.
Other symptoms are that the machine
smokes during steady operation.
Low oil pressure
Full water quantity at steam stage
NEPTUNE 4 FA_EN_Ver.2.0_ 22/11
Troubleshooting
Cause
The hardness of the water
Air deficiency.
Bad oil/air mixture.
Unfinished combustion.
Unstable ignition.
Leaky solenoid valve on pump
Y1.
Incorrect adjustment.
Filter blocked, defective pump. Replace filter/pump. Empty and
Mechanical defect of by-pass
valve or adjustment.
Remedy
Descale boiler tube.
Check air adjustment and fan at-
tachment to boiler.
Check oil pressure and oil quality.
Replace the oil nozzle. Adjust air
diffuser.
Check bottom insulation, boiler top
gasket between tube and inner
boiler jacket in top cover.
Check burner tube.
Check electrodes. Adjust the air
quantity (less air).
Check/replace solenoid valve Y1.
Adjust pump pressure
(see page 45).
clean tank.
Check by-pass valve.