Mitsubishi Electric PURY-P72 Service Handbook page 185

Hide thumbs Also See for PURY-P72:
Table of Contents

Advertisement

[VIII Test Run Mode J
Outdoor unit model
Operation
PURY-P216TSHMU-A
PURY-P120THMU-A
T
PURY-P96THMU-A
Model name of BC controller
CMB-P1013NU-GA
Ambient
Indoor
21.1"C/- [70"F/-J
tempera-
DBIWB
ture
Outdoor
8.3°C/6.1°C
[47°F/43°FJ
No. of connected units
6
Unit
Indoor unit
No. of units in operation
6
Model
-
36/36/36/36/36/36
Operating
conditions
Main pipe
5
[16-3/18"J
Piping
Branch pipe
m
10 [32-3/4'1
[ftJ
Total pipe length
65 [213-1/4'1
Fan speed
-
Hi
Amount of refrigerant
kg
43.0 [95]
flbs-oz]
Electric current
A
54.0
Outdoor
Voltage
V
230
unit
Compressor frequency
Hz
81
71
LEV open-
Indoor unit
350/350/350/350/350/350
Pulse
ing
BC controller (1/2/3)
110/110/1120
High pressure(63HS1)/
2.62/0.64
2.62/0.68
Pressure
Low pressure(63LS)
MPa
[380/92J
[380/98]
BC controller on the liquid side(PS1)1
[psiJ
2.60/2.27
Intermediate part(PS3)
[377/329]
Discharge (TH4)
73 [163J
80 [176J
Heat exchanger outlet
2 [36]
0 [32]
(TH6)
Outdoor
Accumulator inlet
-1
[3OJ
-2 [28]
Temp. of
unit
each sec-
Accumulator outlet
°C
-1
[30J
-3
[27]
tion
Compressor inlet
["FJ
[3OJ
[27]
-1
-3
Compressor shell bottom
40 [104J
40 [104]
LEV inlet
33 [91]
Indoor unit
Heat exchanger inlet
68 [154]
HWEOB03A
- 175-
GB