Mitsubishi Electric PURY-P72 Service Handbook page 186

Hide thumbs Also See for PURY-P72:
Table of Contents

Advertisement

[VIII Test Run Mode]
Outdoor unit model
Operation
PURY-P240TSHMU-A
PURY-P120THMU·A
PURY-P120THMU-A
Model name of BC controller
CMB-P1013NU-GA
Ambient
Indoor
21.1°C/- [70°F/-]
tempera-
DBIWB
ture
Outdoor
8.3°C/6.1°C [47°F/43°F]
No. of connected units
7
Unit
Indoor unit
No. of units in operation
7
Model
-
24/36/36/36/36/36/36
Operating
conditions
Main pipe
5 [16-3118"]
Piping
Branch pipe
m
10 [32-3/4"]
[ft]
Total pipe length
75 [229-5/8"]
Fan speed
-
Hi
Amount of refrigerant
kg
44.6 [98]
pbs-oz]
Electric current
A
58.3
Outdoor
Voltage
V
230
unit
Compressor frequency
Hz
81
81
LEV open-
Indoor unit
203/350/350/350/350/350/350
Pulse
ing
BC controller
(1/213)
110/110/1190
High pressure(63HS1 )/
2.57/0.64
2.57/0.64
Low pressure(63LS)
MPa
[372/92]
[372/92]
Pressure
BC controller on the liquid side(PS1)/
[psi]
2.54/2.22
Intermediate part(PS3)
[368/321]
Discharge (TH4)
73 [163]
73 [163]
Heat exchanger outlet
2 [36]
2 [36]
(TH6)
Outdoor
Accumulator inlet
-1
[30]
-1
[30]
Temp. of
unit
each sec-
Accumulator outlet
°C
-1
[30]
-1
[30]
[oF]
tion
Compressor inlet
-1
[30]
-1
[30]
Compressor shell bottom
40 [104]
40 [104]
LEV inlet
28 [82]
Indoor unit
Heat exchanger inlet
67 [153]
HWE0803A
- 176-
GB