Mitsubishi Electric PURY-P72 Service Handbook page 183

Hide thumbs Also See for PURY-P72:
Table of Contents

Advertisement

[VIII Test Run Mode J
Outdoor unit model
Operation
PURY-P168TSHMU-A
PURY-P96THMU-A
1
PURY-P72THMU-A
Model name of BC controller
CMB-P 108N U-GA
Ambient
Indoor
21.1°C/- f70°F/-J
tempera-
DBIWB
ture
Outdoor
8.3°C/6.1°C
[47° F/43° FJ
No. of connected units
5
Unit
Indoor unit
No. of units in operation
5
Model
-
30/30/36/36/36
Operating
conditions
Main pipe
5
[16-3/18"J
Piping
Branch pipe
m
10
[32-3/4"J
[ftJ
Total pipe length
55
[180-1/8'1
Fan speed
-
Hi
Amount of refrigerant
kg
38.5 [85]
[Ibs-ozJ
Electric current
A
42.2
Outdoor
Voltage
V
230
unit
Compressor frequency
Hz
71
48
LEV open-
Indoor unit
295/295/350/350
Pulse
ing
BC controller
(112/3)
110/110/980
High pressure(63HS1)!
2.64/0.68
2.64/0.69
Pressure
Low pressure(63LS)
MPa
[382/98]
[382/335]
BC controller on the liquid side(PS1)1
[psi]
2.60/2.27
Intermediate
part(PS3)
[377/329]
Discharge (TH4)
80 [176J
69 [156]
Heat exchanger outlet
0 [32J
0 [32]
(TH6)
Outdoor
Accumulator inlet
-2 [28J
1 [34J
Temp. of
unit
each sec-
Accumulator outlet
°C
-3 [27J
1 [34J
tion
Compressor inlet
[OFJ
[27]
1 [34J
-3
Compressor shell bottom
40 [104J
40 [104J
LEV inlet
34 [93J
Indoor unit
Heat exchanger inlet
67 [153J
HWE0803A
- 173-
GB