Restrictions On Pipe Length - Mitsubishi Electric PURY-P72 Service Handbook

Hide thumbs Also See for PURY-P72:
Table of Contents

Advertisement

1----
[II Restrictions]
[8] Restrictions on Pipe Length
(1)
System that requires
16 BC
controller ports or fewer <System with only the main
BC
controller or standard
BC
con-
troller>
Outdoor unit
'Use a main BC controller when connecting the outdoor unils of
P144 model
or above.
Indoor
Maximum of 3 unils per port
,Total capacity of
P54
or below I
Branch joint
I
Irdoor
(CMY.Y1025-G2)
I
~
d
B~
c
1
Reducer
(PIl6 -
P181OOdels)
(Supplied will1the BC Controller)
h1
a
Junction
p~
b
(CMY-R16C-J)
Irdoor
Indoor
(P06. P54
models)
(P72
or P96 models)
H
H'
Unit: m
[ttl
Operation
Pipe sections
Allowable length of pipes
Length
Total pipe length
A-+B-+a-+b-+c-+d
Refer to the restrictions on the total piping
length
in
the graph on the next page.
Total pipe length from the outdoor unit
A-+B+d
165 [541] or less
to the farthest indoor unit
(Equivalent length 190 [623] or less)
Between outdoor unit and BC control-
A
110 [360] or less
ler
Between BC controller and indoor unit
B-+d
40 [131] or less'
1
Height
Outdoor unit
H
50 [164] or less
difference
Between indoor
above indoor unit
and outdoor units
Outdoor unit be-
H'
40 [131] or less
low indoor unit
Between indoor unit and BC controller
h1
15[49](10[32]) or less
'2
Between indoor units
h2
15[49](10[32]) or less '2
*1. When the overall pipe length between the BC controller and the farthest indoor unit exceeds 40m [131
ttl,
observe the
restrictions in the figure titled "Restrictions on pipe length" below. (Except the P96 models)
*2. When the capacity of the connected indoor units is P72 or above, use the figures in the parentheses as a reference.
Note
I
1) To connect the P72 or P96 models of indoor units, use an optional junction pipe kit (Model: CMY-R160-J).
2) Do not connect the P72 or P96 models of indoor units and other models of indoor units at the same port.
3) Note the following when connecting multiple indoor units to a single port.
'Those indoor units connected to the same port must be installed in the same room.
'Set the indoor temperature via the connected remote controller, and when connecting multiple remote controllers, configure
these controllers as a group by making appropriate settings. These indoor units can only be operated in the same mode.
HWE0803A
- 43-
GB