Mitsubishi Electric PURY-P72 Service Handbook page 127

Hide thumbs Also See for PURY-P72:
Table of Contents

Advertisement

1 - - -
[VI
Refrigerant Circuit]
Part
Symbols
Notes
Usage
Specifications
Check method
name
(functions)
Thermis- TH3
Controls defrosting during heating
Degrees Celsius
Resistance
tor
(Pipe
operation
Ro
= 15kQ
check
tem perature)
R1lI80= 3460
1
1
TH7
1) Detects outdoor air tempera-
RI = 15expl3460
(273+i -
m}l
(Outdoor tem-
ture
perature)
2) Controls fan operation
0°C[32°F] :15kohm
TH5
Fan operated on the 63LS and
10°C[50°F] :9.7kohm
TH5 values.
20°C[68°F] :6.4kohm
25°C[77°F] :5.3kohm
TH6
Controls defrosting during heating
30°C[86°F] :4.3kohm
operation
40°C[1 04OF] :3.1 kohm
THHS
Controls inverter cooling fan
Degrees Celsius
Inverter
based on THHS temperature
heat sink tem-
Roo
= 17kll
R251120 = 4016
perature
RI= 17expl4016
(27~+1- 3~3)1
THBOX
Control box in-
ternal tempera-
0°C[32°F] :161 kohm
ture detection
10° C[50° F) :97kohm
20°C[68°F] :60kohm
25°C[77°F] :48kohm
30°C[86°F] :39kohm
40°C[104°F] :25kohm
Sole-
SV1a
1) High/low pressure bypass at
AC208-230V
Continuity
noid
Discharge-suc-
start-up and stopping, and
Open while being poweredl
check with a
valve
tion
capacity control during low-
closed while not being pow-
tester
bypass
load operation
ered
SV2
2) High-pressure-rise preven-
tion
SV4a - SV4d
Controls outdoor unit heat ex-
Heat
changer capacity
exchanger
capacity control
SV5b
Prevents high-pressure-rise
AC208 -230V
Heat
Controls defrost cycle
Closed while being poweredl
exchanger
open while not being powered
capacity control
SV5c
Allows the refrigerant to pass
AC208 -230V
through the bypass pipe to pre-
Open while being poweredl
vent an accumulation of liquid re-
closed while not being pow-
frigerant
ered
SV9
High-pressure-rise prevention
AC208 -230V
Open while being poweredl
closed while not being pow-
ered
Heater
CH11
Heats the refrigerant in the com-
Cord heater
Resistance
pressor
P72 model
cheCk
1035 ohm 51W
P96, P120 models
928 ohm 57W
4-way
21S4a
Changeover between heating and
AC208-230V
Continuity
valve
cooling
Dead: cooling cycle
check with a
Live: heating cycle
tester
HWEOB03A