Mitsubishi Electric PURY-P72 Service Handbook page 184

Hide thumbs Also See for PURY-P72:
Table of Contents

Advertisement

[VIII Test Run Mode J
Outdoor unit model
Operation
PURY-P192TSHMU-A
PURY-P96THMU-A
PURY-P96THMU-A
Model name of BC controller
CMB-P108NU-GA
Ambient
Indoor
21.1°C/- [70°F/-J
tempera-
DBIWB
ture
Outdoor
8.3°C/6.1°C [47°F/43°F]
No. of connected units
6
Unit
Indoor unit
No. of units in operation
6
Model
-
30/30/30/30/36/36
Operating
conditions
Main pipe
5 [16-3/18"]
Piping
Branch pipe
m
10 [32-3/41
[ft]
Total pipe length
65 [213-1/41
Fan speed
-
Hi
Amount of refrigerant
kg
42.4 [93]
[Ibs-oz]
Electric current
A
44.2
Outdoor
Voltage
V
230
unit
Compressor frequency
Hz
71
71
LEV open-
Indoor unit
295/295/295/295/350/350
Pulse
ing
BC controller
(1/213)
110/110/1050
High pressure{63HS1)/
2.67/0.68
2.79/0.58
Pressure
Low pressure{63LS)
MPa
[387/98]
[405/81J
BC controller on the liquid side(PS1)/
[psi]
2.63/2.31
Intermediate part{PS3)
[381/335J
Discharge (TH4)
80 [176]
80 [176]
Heat exchanger outlet
0 [32]
0 [32]
(TH6)
Outdoor
Accumulator inlet
-2 [28]
-2 [28]
Temp. of
unit
each sec-
Accumulator outlet
°C
-3 (27)
-3 (27)
[oF]
tion
Compressor inlet
-3 (27)
-3 (27)
Compressor shell bottom
40 [104]
40 [104]
LEV inlet
38 [100]
Indoor unit
Heat exchanger inlet
70 [158]
HWEOB03A
- 174-
GB