Mitsubishi Electric PURY-P72 Service Handbook page 181

Hide thumbs Also See for PURY-P72:
Table of Contents

Advertisement

- -
- - - - - - - - -
- - - -
[VIII
Test Run Mode]
Outdoor unit model
Operation
PURY-P240TSHMU-A
PURY-P120THMU-A
I
PURY-P120THMU-A
Model name of BC controller
CMB-P1013NU-GA
Ambient
Indoor
26.7°C/19.4 °c [80°F/67°F]
tempera-
DBIWB
ture
Outdoor
35°C/- [95°F/-]
No. of connected units
7
Unit
Indoor unit
No. of units in operation
7
Model
-
24/36/36/36/36/36/36
Operating
conditions
Main pipe
5
[16-3/8'1
Piping
Branch pipe
m
10
[32-3/4"]
[ft]
Total pipe length
75
[229-5/8"]
Fan speed
-
Hi
Amount of refrigerant
kg
44.6 [98]
[Ibs-oz]
Electric current
A
60.2
Outdoor
Voltage
V
230
unit
Compressor frequency
Hz
75
75
LEV open-
Indoor unit
2001275/275/275/275/275/275
Pulse
ing
BC controller
(112/3)
2000/2000/290
High pressure(63HS1
y
2.8210.89
2.8210.89
Pressure
Low pressure(63LS)
MPa
[409/129]
[409/129]
BC controller on the liquid side(PS1)1
[psi]
2.73/2.73
Intermediate part(PS3)
[395/395]
Discharge (TH4)
82 [180]
82 [180]
Heat exchanger outlet
43 [109]
43 [109]
(TH3)
Outdoor
Accumulator inlet
8 [46]
8 [46]
Temp. of
unit
each sec-
Accumulator outlet
°c
8 [46]
8 [46]
tion
Compressor inlet
[oF]
20 [68]
[68]
20
Compressor shell bottom
42 [108J
42 [108]
LEV inlet
22 [72]
Indoor unit
Heat exchanger inlet
11
[52]
HWEOB03A
- 171 -
GB