Mitsubishi Electric PURY-P72 Service Handbook page 141

Hide thumbs Also See for PURY-P72:
Table of Contents

Advertisement

[VII Control J
(2)
ME remote controller (PAR-F27MEA)
Set the address of the remote controller with the rotary switch.
o
aJ(i!
o t : j
C::::>C::::>C:>QOO
Q:)Q)Qc;::)oo
Remote controller unit
Rotary switch
~~
1
D's digit
1
's digit
(left)
(right)
Example:
In
case of address 108
Address setting range
Setting method
Main remote controller
101-150
Add 100 to the smallest address of all the indoor units in the
same group.
Sub remote controller
151-200
Add 150 to the smallest address of all the indoor units in the
same group.
Setting of rotary switch
Address No.
01-99*1
101-199 with the 1OD's digit automatically being set to
1'2
00
200
*1. At factory shipment, the rotary switch is set to 01.
*2. The address range that can be set with the
ME remote controller is between 101 and 200. When the dials are set to
a number between 01 and 99, the 100's digit is automatically set to [1J. When the dials are set to 00, the 100's digit is
automatically set to [2J.
Note
I
To set addresses, use a precision slotted screw driver [2.0 mm [0.08 in] (wl], and do not apply than 19.6N.
The use of any other tool or applying too much load may damage the switch.
4.
Switch functions <BC controller> (Control board)
Switch
Function
Function according to switch setting
Switch setting timing
OFF
ON
1
Model setting
R410A
-
Always leave this switch to OFF.
2-5
-
-
-
-
SW4
6
No. of ports
*1
1
2
Before being energized
7,8
-
-
-
-
1 - 6
-
-
-
-
SW5
7
-
-
-
-
8
-
-
-
-
*1. When a junction pipe kit was used to merge two ports to connect the indoor units with a total capacity of between P31
and P54, tum DIP SW4-6 to ON. When connecting a main and a sub BC controller, change the SW setting on only the
main BC controller.
(It
is not necessary to change the SW setting on the sub BC controller. )
HWEOB03A
- 131 -
GB