[ II Restrictions ]
II Restrictions

[1] System configuration

1. Table of compatible indoor units
The table below summarizes the types of indoor units that are compatible with different types of outdoor units.
(1) Standard combinations
Outdoor
Composing units
units
200
-
250
-
400
200
500
250
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
HWE08110
Maximum total capacity
of connectable indoor
units
-
100 - 260
-
125 - 325
200
200 - 520
250
250 - 650
Maximum number
of connectable
indoor units
17
P15 - P250 models
R410A series indoor units
21
34
43
- 17 -
Types of connectable
indoor units
GB