Mitsubishi Electric PUHY-HP200 Service Handbook page 87

Table of Contents

Advertisement

[ VII Control ]
Switch
Function
Test run mode: en-
1
abled/disabled
Test run mode: ON/
2
OFF
Defrost start temper-
3
ature
Defrost end temper-
4
ature
Target evaporating
5
temperature setting
SW3
Temperature unit
6
setting
Target condensing
7
temperature setting
for heating
8
Model setting
9
(To change the external
static pressure setting)
Model setting
10
(To change the external
static pressure setting)
1
2
Refrigerant amount
3
adjustment
Low-noise mode/
4
step demand switch-
ing
SW4
Automatic cooling/heat-
5
ing switchover (IC with
the minimum address)
Cumulative compressor
6
operation time data dele-
tion
7
8
9
10
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason.
2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units.
B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective.
C: The setting is effective for the unit on which the setting is made.
3) The noise level is reduced by controlling the compressor frequency and outdoor fan rotation speed.
Setting of CN3D is required.(page 24)
4) The table below shows the combination of SW2-9 and SW3-5 settings and the target evaporating temperature setting that
corresponds to each combination.
SW3-5
5) Refer to VII [2] Controlling the Outdoor Unit -7- Defrost Operation Control for details.(page 87)
HWE08110
Function according to switch setting
OFF
SW3-2 disabled
Stops all ICs
-10°C [14°F]
10°C [50°F]
Depends on the setting combination with
the SW2-9 setting (Note 4)
°C
49°C [120°F]
-
-
Outdoor standard
static pressure
High static pressure
60Pa
-
-
-
-
Normal operation
mode
Low-noise mode
(Note 3)
Normal operation
mode
Cumulative compressor
operation time data is
retained.
-
-
-
-
-
-
-
-
Switch
OFF
ON
ON
SW3-2 enabled
Anytime after power on
Sends a test-run
After power on and when
signal to all IC
SW3-1 is on.
-5°C [23°F]
Anytime after power on
Anytime after power on
5°C [41°F]
(except during defrost op-
eration)
Anytime after power on
°F
Anytime after power on
53°C [127°F]
-
Outdoor high static
Before being energized
pressure
High static pressure
Before being energized
30Pa
-
-
Anytime after being energized
(except during initial startup
Refrigerant amount
mode.
adjust mode
Automatically cancelled 90
minutes after compressor
startup)
Step demand mode Before being energized
Automatic cooling/
Before being energized
heating switchover
Cumulative compressor
Anytime after power on (when
operation time data is
the unit is turned on)
deleted.
-
-
-
-
SW2-9
OFF
0°C [32°F]
-2°C [28°F]
- 78 -
Units that re-
quire switch
Switch setting timing
OFF
ON
OC
C
-
-
C
C
-
-
C
C
-
-
-
-
ON
-4°C [25°F]
-6°C [21°F]
setting
Note.2
OS
A
-
A
-
B
B
B
B
A
-
C
A
-
-
-
C
C
-
-
-
-
A
-
C
A
-
C
-
-
-
-
-
-
-
-
GB

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hp250yhm-aHp500yshm-aPuhy-hp400

Table of Contents