Mitsubishi Electric PUHY-HP200 Service Handbook page 216

Table of Contents

Advertisement

[ IX Troubleshooting ]
Discharge pipe
Compressor covers (left)
(The inside of the compressor
cover is lined with sound
insulation material.)
4. Remove the compressor cover (top, left, and right), the compressor wires, and
the crankcase heater. When brazing the pipes, make sure that the insulation in
the compressor cover and the seal material are not damaged.
5. Remove the fixing gasket, the gasket, the mounting plate, and the mounting
support metal. Then, replace the compressor after debrazing the discharge
pipe, the suction pipe, and the injection pipe.
HWE08110
Compressor covers (top)
(The inside of the compressor cover
is lined with sound insulation material.)
Gasket
Injection port
Terminal block box
Mounting plate
- 207 -
Seal material
Suction piping
Compressor covers (right)
(The inside of the compressor
cover is lined with sound
insulation material.)
Crankcase heater
Fixing gasket
Mounting support metal
GB