Mitsubishi Electric PUHY-HP200 Service Handbook page 139

Table of Contents

Advertisement

[ IX Troubleshooting ]
1. Error Code
2600
Water leakage
2. Cause, check method and remedy
Check that water does not leak from the pipes in such as the humidifier.
1. Error Code
2601
Water supply cutoff
2. Cause, check method and remedy
(1)
The water tank of the humidifier is empty.
(2)
The solenoid valve for humidification is OFF.
(3)
Disconnected float switch
(4)
Poor operation of float switch
(5)
Frozen water tank
HWE08110
Cause
Check method and remedy
Check the amount of supply water.
Check for the solenoid valve and for the connection.
Check the connector.
Check the connecting part.
Check for the float switch.
Turn off the power source of the water tank to defrost, and
turn it on again.
- 130 -
GB

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hp250yhm-aHp500yshm-aPuhy-hp400

Table of Contents