[ VIII Test Run Mode ]
(2) Heating operation
Ambient
tempera-
ture
Indoor
unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
SC (LEV1)
LEV open-
ing
LEV2
LEV4
High pressure (after O/S)/low pres-
Pressure
sure (before accumulator)
Outdoor
unit
Temp. of
each sec-
tion
Indoor
unit
HWE08110
Operation
Indoor
Outdoor
No. of connected units
No. of units in operation
Model
Main pipe
Branch pipe
Total pipe length
Discharge (TH4)
Heat exchanger outlet
(TH3)
Accumulator inlet
Accumulator outlet
Compressor inlet
Compressor shell bottom
LEV inlet
Heat exchanger outlet
PUHY-HP200YHM-A
21.1°C/ - [70°F/ - ]
DB/WB
8.3°C/6.1°C [47°F/43°F]
2
Unit
2
-
100/100
5 [16-3/8 ]
m [ft]
10 [32-3/4 ]
25 [82]
-
Hi
kg
13.8
[30-1/2]
[lbs-oz]
A
11.0
V
380
Hz
55
325/325
0
Pulse
1400
0
MPa
2.81/0.66 [408/96]
[psi]
84 [183]
-2 [28]
-2 [28]
-2 [28]
°C [°F]
-2 [28]
40 [104]
38 [100]
80 [176]
- 110 -
Outdoor unit model
PUHY-HP250YHM-A
21.1°C/ - [70°F/ - ]
8.3°C/6.1°C [47°F/43°F]
2
2
125/125
5 [16-3/8 ]
10 [32-3/4 ]
25 [82]
Hi
13.8
[30-1/2]
15.4
380
72
406/406
0
1400
0
2.87/0.67 [416/97]
84 [183]
-3 [26]
-3 [26]
-3 [26]
-3 [26]
40 [104]
39 [102]
80 [176]
GB