17. Fuel Drain Plug — Remove this plug to drain fuel
from the fuel tank.
18. Frame Ground Lug — Connect a ground strap
between this lug and a ground rod. Make sure that the
ground rod is inserted deep into the ground to provide
a good earth ground. Consult with local Electrical and
Safety Codes for proper connection based on condition
of use.
19. 120/240V Output Receptacle — CS6369 twist-lock
receptacle provides 240 V, 60 Hz output at 25 amps,
or 120V, 60 Hz at 50 amps (X2), depending on the
position of the full power switch.
20. 120/240V Output Receptacle — NEMA L14-30R
twist-lock receptacle provides 240 V, 60 Hz output at
25 amps, or 120V, 60 Hz at 30 amps (X2), depending
on the position of the full power switch.
21. 120V Output Receptacles — NEMA 5-20R twist-lock
receptacle provides 120V, 60 Hz output at 30 amps,
depending on the position of the full power switch.
DA7000SSA2/SSA2GH GENERATOR• OPERATION AND PARTS MANUAL — REV. #0 (03/26/15) — PAGE 19
26
22
18
Figure 4. Generator Components (2 of 3)
COMPONENTS (GENERATOR)
27
25
19
21
20
22. Duplex Receptacle — NEMA 5-20R receptacle
provides 120V, 60 Hz output at 20 amps.
23. 30 Amp Breaker (for L14-30R) — Single-pole, 30 Amp
circuit breaker protects the 120V twist-lock receptacle.
When starting the generator, always have this circuit
breaker placed in the "OFF" position.
24. 30 Amp Breaker (for L5-30R) — Single-pole, 30 Amp
circuit breaker protects the 120V twist-lock receptacle.
When starting the generator, always have this circuit
breaker placed in the "OFF" position.
25. 20 Amp Breaker (for 5-20R) — Single-pole, 20 Amp
circuit breaker protects the 120V duplex receptacle.
When starting the generator, always have this circuit
breaker placed in the "OFF" position.
26. GFCI Sensing Module — Interrupts power, by opening
the main breaker, when a ground fault exists.
27. Main Breaker — 2-pole, 25 Amp circuit breaker
protects the generator from short circuiting or
overloading. When starting the generator, always have
this circuit breaker placed in the "OFF" position.