Chapter 2. SPECIFICATIONS
2.2

Performance Specifications

Table. 2.2 shows performance specifications of the PID control module.
Setting range
of PID
constants
Setting range : SV (Set Value)
Input range : PV (Process Value)
Output range : MV (Manipulated Value)
Setting range : M_MV
(Manually Manipulated Value)
LED
Number of PID control loops
Control action
Control cycle
Processing type
Internal current consumption
Items
Proportional constant (P)
Integral constant (I)
Derivative constant (D)
RUN / STOP
NORMAL/ERROR
Weight
[Table. 2.2 Performance Specifications]
Specifications
K7F-PIDA
0.01 ~ 100.00
( When integral and derivative constants are set to
0.0 sec, proportional action is applied.)
0.0 ~
( When integral constant is set to 0.0 sec, integral action
shall not be applied.)
0.0 ~
( When derivative constant is set to 0.0 sec, derivative
action shall not be applied.)
0 ~ 16,000
0 ~ 16,000
0 ~ 16,000
0 ~ 16,000
RUN : The run LED of corresponding loops ON
STOP : The run LED of corresponding loops OFF
Normal
: RUN LED ON
Error
: RUN LED flickering
32 loops
Forward/Reverse action control is available.
0.1 sec
Measured value derivative type
(Pre-derivative type)
0.3 A
370 g
2 - 2
K4F-PIDA
3000.0 sec
3000.0 sec
8 loops
0.2 A
190 g