Application Programming; A Program For Controlling An Electric Furnace - LG K4F-PIDA User Manual

Master-k programmable logic controller
Table of Contents

Advertisement

Chapter 6. PROGRAMMING

6.2 Application Programming

6.2.1 A Program for Controlling an Electric Furnace

(with Applying the A/D Conversion Module, PID Control Module and D/A Conversion Module)
1) System Configuration
K7S-
122S
1)
Initial Settings
(1)
PID control module
A) Specifying used loop : loop 0
B) Specifying forward/reverse action : forward action
C) Setting SV: 12800
D) Specifying auto/manual processing : auto processing
(2)
A/D conversion module
A) Specifying used channel: channel 0
B) Specifying output data type: -192 to 16191
C) Setting filter constant: 50
(3)
D/A conversion module
A) Specifying used channel: channel 0
B) Specifying input data type: -192 to 16191
C) Output when no channel is used or the CPU module is in the stop state : The median value of the output range is
output.
2)
Descriptions of the Program
(1)
A temperature 0 to 200 C from the temperature sensor is converted into an analog signal 4 to 20 mA and then
the signal is input to the channel 0 of the A/D conversion module channel and converted into a digital value 9600
to 16000.
K7S-
K7X-
K7X-
30AS
310S
310S
K7F-
K7F-
K7F-
AD4A
PIDA
DI4A
Ch. 0
Loop 0
Ch. 0
10 - 3
K7S-
K7Y-
132S
201S

Advertisement

Table of Contents
loading

This manual is also suitable for:

K7f-pida

Table of Contents