Rinnai ENERGYSAVER EX08C Installation Fundamentals page 65

Direct vent wall furnace
Hide thumbs Also See for ENERGYSAVER EX08C:
Table of Contents

Advertisement

PCB Adjustments for extended venting or high altitude
With power off, remove front cover and press the test button on the PCB. Use the
temperature arrows on the control panel to set as follows
For installations from 0-2000' above sea level
For installations from 2001-5200' above sea level
NG
For installations from 5201-7700' above sea level
For installations from 7701-10,200' above sea level
For installations from 0-2000' above sea level
For installations from 2001-5200' above sea level
LP
For installations from 5201-7700' above sea level
For installations from 7701-10,200' above sea level
*default setting
MODEL: EX11C
(See the previous slide for an illustration)
with a vent length of 0 to 7 ft
with a vent length of 7 to 13 ft
with a vent length of 0 to 7 ft
with a vent length of 7 to 13 ft
with a vent length of 0 to 7 ft
with a vent length of 7 to 13 ft
with a vent length of 0 to 7 ft
with a vent length of 7 to 13 ft
with a vent length of 0 to 13 ft
with a vent length of 0 to 13 ft
with a vent length of 0 to 13 ft
with a vent length of 0 to 13 ft
Set code to A1*
Set code to A5
Set code to A2
Set code to A6
Set code to A3
Set code to A7
Set code to A4
Set code to A8
Set code to L1* or L5
Set code to L2 or L6
Set code to L3 or L7
Set code to L4or L8
65